Underfloor Power Solutions
Underfloor Power Solutions
Raised floors are still the standard in the data center industry, with power cables running underfloor and data or network cables running overhead. Because it's the most common data center configuration does that make it right for your data center? That's hard to say, it is a personal choice with a lot of pros and cons to be considered that should be based on thoughtful consideration.
PDU Cables branch circuit power distribution cables are being installed every day, below a raised floor and overhead with ladder racks and in a cable tray.
To accommodate underfloor power cabling, PDU Cables, offers liquid tight flexible metal conduit (Liquid Tight) in eleven colors as the best choice for underfloor cabling. You also have your choice of different weather proof receptacle bell boxes, and a broad selection of mounting hardware designed to elevate the receptacles up off the floor and within easy reach of a pulled floor tile.
Cable Types
Liquid Tight Flexible Metal Conduit (LFMC)
Flexible Metal Conduit - (RWS & RWA) - Field Wires
SO Cords - Molded Cord Assemblies
Device Types
The NEMA (National Electrical Manufacturers Association) pattern and numbering system is made up of four main identifiers. The first identifier can be a blank space or have the letter L. This determines whether it is a straight or locking blade device. The second identifier is a number. The first number in a NEMA listing determines the voltage rating. The third identifier is a number and identifies the amperage rating of the device. The fourth identifier is a letter. This identifier determines whether the device is a plug, P, or a receptacle/outlet, R.
Plug & Receptacle Configuration Charts:
NEMA Straight Blade Plugs & Receptacles
NEMA Locking Plugs & Receptacles
Russell Stoll Pin & Sleeve Devices
RussellStoll® receptacles (IBM type) are available in box style or in-line connector versions. The housings are corrosion resistant and cast aluminum manufactured. The receptacles are watertight, arc-resistant and constructed with a molded plastic interior.
Part Number | Receptacle | Service | Breaker | Wire | Conduit Inches | ||||
Volts | AMP | Phase | P | A | Quantity | Size | |||
IBM A | RS 3913 | 208 | 20 | 1 | 2 | 20 | 3 | 12 AWG | .5 |
IBM A-U1 | RS 3913-U1 | 120 | 20 | 1 | 1 | 20 | 3 | 12 AWG | .5 |
IBM A-U2 | RS 3913-U2 | 208 | 15 | 1 | 2 | 15 | 3 | 12 AWG | .5 |
IBM B | RS 3914 | 208 | 15 | 3 | 3 | 15 | 4 | 12 AWG | .5 |
IBM C | RS 3933 | 208 | 30 | 1 | 2 | 30 | 3 | 10 AWG | .5 |
IBM D | RS 3934 | 208 | 30 | 3 | 3 | 30 | 4 | 10 AWG | .5 |
IBM E | RS 7428 | 208 | 60 | 3 | 3 | 60 | 4 | 6 AWG | .75 |
IBM F | RS JCS1034H | 208 | 100 | 3 | 3 | 100 | 4 | 3 AWG | 1.25 |
IEC Cables Pin & Sleeve Devices
IEC receptacles are Pin and Sleeve style, watertight, made with rugged nylon housings and color coded by amperage. The shrouding on the IEC devices protects the pins from abuse and are arc-resistant.
IEC 60309 "Pin & Sleeve" Configuration Chart
Part Number | Receptacle | Service | Breaker | Wire | Conduit Inches | ||||
Volts | AMP | Phase | P | A | Quantity | Size | |||
320C6W | A3206C6W | 250 | 20 | 1 | 2 | 20 | 3 | 12 AWG | .5 |
330C6W | 330C6W | 250 | 30 | 1 | 2 | 30 | 3 | 10 AWG | .5 |
360C6W | A3606C6W | 250 | 60 | 1 | 2 | 60 | 3 | 6 AWG | .75 |
420C9W | 420C9W | 208 | 20 | 3 | 3 | 20 | 4 | 12 AWG | .5 |
430C7W | 430C7W | 480 | 30 | 3 | 3 | 30 | 4 | 10 AWG | .5 |
430C9W | 430C9W | 250 | 30 | 3 | 3 | 30 | 4 | 10 AWG | .5 |
460C9VO | 460C9VO | 208 | 60 | 3 | 3 | 60 | 4 | 6 AWG | .75 |
460C9W | 460C9W | 208 | 60 | 3 | 3 | 60 | 4 | 6 AWG | .75 |
4100C9W | 4100C9 | 250 | 100 | 3 | 3 | 100 | 4 | 2 AWG | 1.25 |
560C9W | 560C9W | 208 | 60 | 3 | 3 | 60 | 5 | 6 AWG | 1.0 |
5100C9W | 5100C9W | 208 | 100 | 3 | 3 | 100 | 5 | 2 AWG | 1.25 |
NEMA Standard Straight Blade Devices
Part Number | Receptacle | Service | Breaker | Wire | Conduit Inches | ||||
Volts | AMP | Phase | P | A | Quantity | Size | |||
515R1* | 5261 | 120 | 15 | 1 | 1 | 15 | 3 | 12 AWG | .5 |
515R2* | 5262 | 120 | 15 | 1 | 1 | 15 | 3 | 12 AWG | .5 |
515R4* | 5262 (2) | 120 | 15 | 1 | 1 | 15 | 3 | 12 AWG | .5 |
520R1* | 5361 | 120 | 20 | 1 | 1 | 20 | 3 | 12 AWG | .5 |
520R2* | 5362 | 120 | 20 | 1 | 1 | 20 | 3 | 12 AWG | .5 |
520R4* | 5362 (2) | 120 | 20 | 1 | 1 | 20 | 3 | 12 AWG | .5 |
530R1* | 9308 | 120 | 30 | 1 | 1 | 30 | 3 | 10 AWG | .5 |
550R1 | 9360 | 120 | 50 | 1 | 1 | 50 | 3 | 8 AWG | .5 |
615R1* | 5661 | 208 | 15 | 1 | 2 | 15 | 3 | 12 AWG | .5 |
615R2* | 5662 | 208 | 15 | 1 | 2 | 15 | 3 | 12 AWG | .5 |
615R4* | 5662 (2) | 208 | 15 | 1 | 2 | 15 | 3 | 12 AWG | .5 |
620R1* | 5461 | 208 | 20 | 1 | 2 | 20 | 3 | 12 AWG | .5 |
620R4* | 5462 (2) | 208 | 20 | 1 | 2 | 20 | 3 | 12 AWG | .5 |
630R1* | 9330 | 208 | 30 | 1 | 2 | 30 | 3 | 10 AWG | .5 |
1420R1 | 8410 | 120/208 | 30 | 1 | 2 | 30 | 4 | 12 AWG | .5 |
1430R1 | 9430 | 120/208 | 30 | 1 | 2 | 30 | 4 | 10 AWG | .5 |
1450R1* | 9450 | 120/208 | 50 | 1 | 2 | 50 | 4 | 8 AWG | .75 |
*Available with isolated ground. All NEMA Type cable assemblies are available in daisy-chain configurations.
Part Number | Receptacle | Service | Breaker | Wire | Conduit Inches | ||||
Volts | AMP | Phase | P | A | Quantity | Size | |||
L515R1* | 4710 | 120 | 15 | 1 | 1 | 15 | 3 | 12 AWG | .5 |
L515R2* | 4700 | 120 | 15 | 1 | 1 | 15 | 3 | 12 AWG | .5 |
L520R1* | 2310 | 120 | 20 | 1 | 1 | 20 | 3 | 12 AWG | .5 |
L530R1* | 2610 | 120 | 30 | 1 | 1 | 30 | 3 | 10 AWG | .5 |
L615R1* | 4560 | 208 | 15 | 1 | 2 | 15 | 3 | 12 AWG | .5 |
L615R2* | 4550 | 208 | 15 | 1 | 2 | 15 | 3 | 12 AWG | .5 |
L620R1* | 2320 | 208 | 20 | 1 | 2 | 20 | 3 | 12 AWG | .5 |
L630R1* | 2620 | 208 | 30 | 1 | 2 | 30 | 3 | 10 AWG | .5 |
L715R1 | 4760 | 208 | 15 | 1 | 2 | 15 | 3 | 12 AWG | .5 |
L1420R1* | 2410 | 120/208 | 20 | 1 | 2 | 20 | 4 | 12 AWG | .5 |
L1430R1* | 2710 | 120/208 | 30 | 1 | 2 | 30 | 4 | 10 AWG | .5 |
L1520R1* | 2420 | 208 | 20 | 3 | 3 | 20 | 4 | 12 AWG | .5 |
L1530R1* | 2720 | 208 | 30 | 3 | 3 | 30 | 4 | 10 AWG | .5 |
L2120R1* | 2510 | 208 | 20 | 3 | 3 | 20 | 5 | 12 AWG | .5 |
L2130R1* | 2810 | 208 | 30 | 3 | 3 | 30 | 5 | 10 AWG | .5 |
*Available with isolated ground. All NEMA Type cable assemblies are available in daisy-chain configurations.