Cable grommet with nylon brush significanty reduces bypass airflow overall as operating data center's room temperature is reduced by 8 degrees Celsius.
AbstractData Center Air Management Solutions was interested in testing the performance characteristics between two major brands of cable grommets which utilize nylon brushes to reduce bypass airflow associated with raised access floors. The tests were conducted utilizing the maximum under-floor static pressures referenced by Liebert Corporation for their standard process cooling equipment; DS units @ 0.2”WG, Challenger @ 0.3”WG and Deluxe System 3 units @ 0.5”WG. Under these varied conditions, we simulated four (4) typical conditions found in nearly every data center to measure the actual bypass airflow; open hole, closed hole w/brushed grommet, grommet w/ ½” cable power, and grommet w/ ¾” cable. We also reviewed an independent client test measuring actual temperatures within an operating data center, both before and after, utilizing cable grommet with nylon brushes. The tests were performed to determine the quality and performance characteristics of utilizing cable grommets with nylon brushes. |
Kenneth A. Rapoport, an engineering honors graduate from the University of Texas (Austin) is the founder and C.E.O. of Electronic Environments Corporation, and a principal with Data Center Air Management Solutions (DCAMS), LLC. Mr. Rapoport has over 30+ years of mission critical experience in data centers, both domestically and internationally. Electronic Environments Corporation has provided Design, Construction, andMaintenance services to data centers throughout the USA for the past 21+ years. DCAMS was established to bring the best data center air distribution & management products to market.

SCFM: Cubic Feet per Minute at Standard Air Conditions 20°C/68°F, 50% RH, 101.325 kPa/14.696psi





8 °C drop in data center temperature
We have a lot of holes cut into the floor tiles which have power, copper and fibre routing through from racks to under the floor. These cut outs allow air to escape, thus reducing the under floor pressure, robbing the fronts of racks (and thus servers) of efficient cooling via the CRAC units which in turn waste a lot of energy and efficiency …
As you can see below, the hole allows a lot of air to escape, but with the Air Guard it’s sealed up with the use of a brush strip, also eliminating the trip hazard and making for a safer working environment behind the racks.
I recorded the temperature of the rack before the installation of this solution and again afterwards, and the difference is significant … The erratic temperatures caused by poor air pressure and cooling are shown below
You can see from the chart below it gave us a drop of at least 8°c, dropping from 30°c down to 22°c with the Air Guard in place and with the door closed and has stayed that way. That is a massive improvement, (the lower temp shown is because the door was open for comparison)
I believe that the use of this solution will aid cooling efficiency, reduce the work load of the CRAC units and in the long term save the DC money on the energy we use. It will also create a safer working environment at the back of the racks. I would like to propose the use of these throughout the Data Centres on all of the holes we currently have.
Ash Burton, Director of Information Technology University of South Hampton, United Kingdom